Daftar Parameter Teknis KYW3-1600
| Model pemutus sirkuit | KYW3-1600 | |||
| Nilai arus Masuk (40 ℃) (A) | 200,400,630,800,1000,1250,1600 | |||
| Arus pengenal n-kutub | 100% masuk | |||
| Nilai tegangan kerja Ue (V) | AC220/230/240、AC380/400/415、AC440/480、AC660/690 | |||
| Frekuensi terukur f (Hz) | 50/60 | |||
| Tegangan isolasi terukur Ui (V) | 1000 | |||
| Tegangan ketahanan impuls terukur Uimp (kV) | 12 | |||
| Tiang nomor kutub | 3,4 | |||
| Catatan waktu istirahat penuh (ms) | ≤25 | |||
| Waktu tutup:2 (mdtk) | ≤60 | |||
| Nilai kapasitas pemutusan hubung singkat tertinggi Icu (nilai efektif) (kA) | AC220V/230V/240V AC380V/400V/415V | 65 | ||
| AC440V/480V AC660V/690V | 50 | |||
| Nilai kapasitas pemutusan arus pendek operasi Ics (nilai efektif) (kA) | AC220V/230V/240V AC380V/400V/415V | 65 | ||
| AC440V/480V AC660V/690V | 50 | |||
| Nilai kapasitas produksi jangka pendek I cm (nilai puncak) (kA) | AC220V/230V/240V AC380V/400V/415V | 145 | ||
| AC440V/480V AC660V/690V | 105 | |||
| Dinilai menahan arus dalam waktu singkat Icw (nilai efektif) 1s (kA) | AC220V/230V/240V AC380V/400V/415V | 55 | ||
| AC440V/480V AC660V/690V | 42 | |||
| Kinerja operasional | Umur listrik (kali) Frekuensi pengoperasian (20 kali/jam) | AC220V/230V/240V AC380V/400V/415V | 10000(200A~630A)、8000(800A~1250A)、6500(1600A) | |
| AC440V/480V AC660V/690V | 8000(200A~630A)、5000(800A~1250A)、3000(1600A) | |||
| Umur mekanis (kali) Frekuensi pengoperasian (60 kali/jam) | Bebas perawatan | 10000 | ||
| Ada pemeliharaan | 20000 | |||
| Metode instalasi | Tipe tetap, tipe laci | |||
| Metode pengkabelan sirkuit utama | Pengkabelan horizontal, pengkabelan vertikal, pengkabelan campuran (horizontal atas dan vertikal bawah), pengkabelan campuran (vertikal atas dan horizontal bawah) | |||
| Dimensi keseluruhan: L×D×T(mm) | Memperbaiki tipe 3P | 259×200,5×318 | ||
| Memperbaiki tipe 4P | 329×200,5×318 | |||
| Tipe laci 3P | 282×305×351,5 | |||
| Tipe laci 4P | 352×305×351,5 | |||
| Berat (kg) | Memperbaiki tipe 3P | 22(200A~630A) | 23(800A~1600A) | |
| Memperbaiki tipe 4P | 34(200A~630A) | 35(800A~1600A) | ||
| Tipe laci 3P | 43(200A~630A) | 44(800A~1600A) | ||
| Tipe laci 4P | 56(200A~630A) | 57(800A~1600A) | ||
Catatan: 1. Waktu putus penuh: Interval waktu dari saat pemutus arus diputus hingga saat waktu busur berakhir.
2. Waktu penutupan: Interval waktu dari saat pemutus arus ditutup hingga saat semua kontak kutub bersentuhan.